Star–delta motor starter
Big motors started directly draw 6–8 times their current. The star–delta starter starts them gently: three contactors, a timed changeover with a pause, an interlock so that star and delta are never on together, and an overload trip that needs a reset.
You need IF, the latch and timers: chapters 1–8 of PLC from zero teach them.
Chapters
How the course works
Structured Text (IEC 61131-3), the language used by industrial engineering environments such as TwinCAT 3 and CODESYS. PLC Studio and the Trainer T8 are VisoTrain’s own training tools. TwinCAT is a registered trademark of Beckhoff Automation GmbH. CODESYS is a registered trademark of CODESYS GmbH. VisoTrain is not affiliated with or endorsed by them.
Syllabus
Level: Intermediate · Time: about 2 hours · You need: IF, latch and timers (chapters 1–8 of PLC from zero).
You learn: star-delta starting, contactor interlocks, dead times between contactors, fault latching and reset.
Chapter 1: Start in star
- Starting a big motor: Say why big motors are started in star, and what the starter does.
- Start and stop in star: Latch the motor on, drive K1 and K2, and measure the star time.
- Lab in PLC Studio: program this part and pass the automatic tests.
Chapter 2: Change over to delta, safely
- The change to delta: dead time and interlock: Switch to delta after a short pause, never with star.
- Lab in PLC Studio: program this part and pass the automatic tests.
Chapter 3: Overload trip and reset
- Overload trip and reset: Stop on an overload, show it, and allow a restart only after a reset.
- Lab in PLC Studio: program this part and pass the automatic tests.
Frequently asked questions
Why is a motor started in star and then switched to delta?
In star each winding gets a lower voltage, so the motor draws about a third of the direct-on-line starting current.
Why a pause between star and delta?
The star contactor needs a moment to open before the delta contactor closes, or the mains would be short-circuited.